EN IEC 62305-3:2024

Protection against lightning - Part 3: Physical damage to structures and life hazard EN IEC 62305-3:2024

Publication date:   Oct 13, 2023

General information

60.60 Standard published   Oct 25, 2024

CENELEC

CLC/TC 81X Lightning protection

European Norm

29.020   Electrical engineering in general | 91.120.40   Lightning protection

Buying

Draft

Language in which you want to receive the document.

Scope

IEC 62305-3:2024 provides the requirements for protection of a structure against physical damage by means of a lightning protection system (LPS), and for protection against injury to human beings due to touch and step voltages in the vicinity of an LPS (see IEC 62305-1).

This document is applicable to the:

a) design, installation, inspection and maintenance of an LPS for structures without limitation of their height,

b) establishment of measures for protection against injury to human beings primarily due to touch and step voltages.

This third edition cancels and replaces the second edition published in 2010. This edition constitutes a technical revision.

This edition includes the following significant technical changes with respect to the previous edition:

a) Minimum thicknesses of metal sheets or metal pipes are given in Table 4 for air-termination systems where it is necessary to prevent hot-spot problems. Maximum temperature rises ΔT (K) and time duration t50 (s) for different thicknesses and long strokes are also given.

b) Cross-reference to the IEC 62561 series is made for the use of reliable, stable, safe and appropriate LPS components.

c) The application of two methods – general and simplified – for separation distance calculation is clarified.

d) Some changes to the requirements for continuity of steel reinforcement are made.

e) Annex C is revised to address comments from IEC subcommittee 31J.

f) Revision of positioning of air-termination conductors are modified according to the three accepted methods. A more precise description of the methods for positioning of the air-termination systems are made according to the complexity of structures to be protected. The main text has been simplified, Annex A has been deleted and all detailed information has been moved to Annex D.

g) Information on the protection of green roofs is introduced in Annex D.

h) Information on the protection of protruding parts on facades of tall buildings is introduced in Annex D.

i) a new definition of “electrically insulated LPS” has been introduced to distinguish it from an LPS both electrically and physically isolated from the structure, with a slight modification of the other LPS definitions.

Life cycle

PREVIOUSLY

PUBLISHED
EN 62305-3:2011

NOW

PUBLISHED
EN IEC 62305-3:2024
60.60 Standard published
Oct 25, 2024