CEN/TS 17889:2024

District heating pipes - Factory made flexible pipe systems - Classification, requirements and test methods for bonded or non-bonded system with thermoplastic reinforced service pipes (TRSP)

Publication date:   Jul 17, 2024

General information

60.60 Standard published   Nov 20, 2024

CEN

CEN/TC 107 Prefabricated district heating and district cooling pipe system

Technical Specification

23.040.07   Pipelines and its parts for district heat

Buying

  Draft

PDF - €18.15

  English  



Buy

Scope

This document specifies classification, general requirements and test methods for flexible, factory made, buried district heating pipe systems with thermoplastic reinforced service pipes (TRSP).
The factory made bonded or non-bonded flexible pipe systems, covered by this document, consists of:
- Thermoplastic reinforced service pipe, which consists of an inner layer made of PE-Xa, a thermoplastic intermediate layer, a reinforcement layer made of para-aramid fibres, an outer thermoplastic layer and a diffusion barrier layer, all with bonded structure;
- Thermal insulation layer;
- Casing made of PE.
Depending on the temperature profile, this document is applicable to a maximum operating temperature of 115 °C and maximum operating design pressure up to 1,6 MPa.
The pipe systems are designed for a service life of at least 30 years.
This document does not apply to cover surveillance systems.
NOTE For higher temperatures or for the transport of other fluids, for example potable water, additional requirements and testing is needed. Such requirements are not specified in this document.
A guideline for testing the pipe assembly is given in Annex D.

Life cycle

NOW

PUBLISHED
CEN/TS 17889:2024
60.60 Standard published
Nov 20, 2024