prEN 1366-14

Fire resistance tests for device installations - Part 14: Partial penetration seals prEN 1366-14

Publication date:   Apr 11, 2024

General information

40.20 DIS ballot initiated: 12 weeks   Apr 11, 2024

CEN

CEN/TC 127 Fire safety in buildings

European Norm

13.220.50   Fire-resistance of building materials and elements | 91.060.10   Walls. Partitions. Façades

Buying

Draft

Language in which you want to receive the document.

Scope

This part of the EN 1366 series specifies a method of test and criteria for the evaluation (including field of direct application rules) of the ability of a partial penetration seal to maintain the fire resistance of a separating element at the position at which it has been penetrated by a device or devices that passes through one face of the element only. Partial penetration seals are used to seal apertures for electrical sockets, downlighters, media devices, cables and any item which requires an opening to be made in one face of the element of construction but does not include a device which passes through both faces. Supporting constructions are used in this part of the EN 1366 series to represent separating elements such as walls or floors. These simulate the interaction between the test specimen and the separating element into which the sealing system is to be installed in practice.
This part of the EN 1366 series is used in conjunction with EN 1363 1.
The purpose of a test described in this part of the EN 1366 series is to assess the integrity and insulation performance of the partial penetration seal, of the penetrating service(s) or device(s) and of the separating element in the surrounding area of the partial penetration seal. Where partial penetration seals are installed in ceilings and floors, the loadbearing capacity shall also be considered.
No information can be implied by the test concerning the influence of the inclusion of such penetrations and penetration seals on the loadbearing capacity of walls.
It is not the intention of this test to provide quantitative information on the rate of leakage of smoke and/or hot gases or on the transmission or generation of fumes. Such phenomena are only to be noted in the test report in describing the general behaviour of test specimens during the test.
Tests in accordance with this part of the EN 1366 series are not intended to supply any information on the ability of the partial penetration seal to withstand stress caused by movements or displacements of the penetrating devices.
The risk of spread of fire downwards cannot be assessed with this test.
Tests in accordance with this part of the EN 1366 series do not address any risks associated with leakage of dangerous liquids or gases caused by failure of the device in case of fire.

Related legislation

Legislation related to this standard

305/2011

Regulation (eu) No 305/2011 of the European Parliament and of the Council of 9 march 2011 laying down harmonised conditions for the marketing of construction products and repealing council directive 89/106/eec

Life cycle

NOW

IN_DEVELOPMENT
prEN 1366-14
40.20 DIS ballot initiated: 12 weeks
Apr 11, 2024