ISO/NP 24269

Reaction to fire test for sandwich panel building systems — Part 1: Small room test, Alternative burner for 13784-1 ISO/NP 24269

General information

10.20 New project ballot initiated   Sep 20, 2023

ISO

ISO/TC 92/SC 1 Fire initiation and growth

International Standard

Scope

It is proposed to add an alternative burner at Annex of ISO 13784-1, which should be in line with ISO
9705-1. As the members of ISO/TC92/SC1/WG7 already know, Annex A (normative) of ISO 9705-1:
2016 prescribes both standard ignition source (burner) and alternative ignition source (burner). On the
other hand, ISO 13784-1 prescribes only the standard ignition source (burner). See Figures 1 and 2.
In the case of standard ignition source, burner configuration is 170 (W) x 170 (D) x 145 (H) mm, and
heat output is 100 kW for the first ten minutes and 300 kW for the last ten minutes. On the other hand,
in the case of alternative ignition source, burner configuration is 305 (W) x 305 (D) x 152 (H) mm, and
maximum net heat output is (162 ± 4) kW.