ISO 10295-2:2009

Fire tests for building elements and components — Fire testing of service installations — Part 2: Linear joint (gap) seals ISO 10295-2:2009

Publication date:   Jan 19, 2009

General information

90.93 Standard confirmed   Oct 26, 2020

ISO

ISO/TC 92/SC 2 Fire containment

International Standard

13.220.50   Fire-resistance of building materials and elements | 91.140.01   Installations in buildings in general

Buying

Published

Language in which you want to receive the document.

Scope

ISO 10295-2:2009 specifies the heating conditions, methods of test and criteria for the evaluation of the ability of a linear joint seal to maintain the fire integrity and thermal insulation of a fire-separating element at the joint being sealed. The purpose of the tests is to assess the integrity and insulation performance of the linear joint seals, including the effects of induced movement in those cases where the joint is designed to accommodate movement and has a width greater than 20 mm.
It is not the intention of this part of ISO 10295-2:2009 to provide quantitative information on the rate of leakage of smoke and/or gases, or on the transmission or generation of fumes, although such phenomena can be recorded in describing the general behaviour of specimens during the test. It is not the intention of this part of ISO 10295-2:2009 to evaluate joint seals where special test procedures already exist, e.g. doors, partitions, penetrations, pipes, ducts and cables.

Life cycle

NOW

PUBLISHED
ISO 10295-2:2009
90.93 Standard confirmed
Oct 26, 2020

CORRIGENDA / AMENDMENTS

PUBLISHED
ISO 10295-2:2009/Cor 1:2009

REVISED BY

ABANDON
ISO/PWI 10295-2