Revised
Specifies general requirements for construction, testing and
marking of electrical apparatus for explosive gas atmospheres.
Applies to electrical apparatus where atmospheric conditions for
the explosion characteristics of the explosive gas atmosphere are
considered as having pressures in the range 80 kPa (0.8 bar) to 110
kPa (1.1 bar) at a temperature in the range -20°C to +60°C.
Atmospheric conditions outside this range may need special
consideration.
Does not apply to devices whose stated electrical parameters do not
exceed any of the values 1-2 V, 0.1 A, 20 µJ or 25 mW, which need
not be certified or marked as required by IEC 79. However, such
devices are subject to the requirements of the various parts of IEC
79 if they are connected to a device which contains a source or a
storage element of electrical energy which could cause the circuit
to exceed these parameters.
Supersedes IEC 79-8 and 79-9.
WITHDRAWN
IEC 60079-8:1969/AMD1:1972 ED1
WITHDRAWN
IEC 60079-8:1969 ED1
WITHDRAWN
IEC 60079-9:1970 ED1
WITHDRAWN
IEC 60079-0:1971 ED1
WITHDRAWN
IEC 60079-0:1983 ED2
99.60
Withdrawal effective
Apr 15, 1998
WITHDRAWN
IEC 60079-0:1983/AMD2:1991 ED2
WITHDRAWN
IEC 60079-0:1983/AMD1:1987 ED2
WITHDRAWN
IEC 60079-0:1998 ED3