EN IEC 61326-3-2:2018

Electrical equipment for measurement, control and laboratory use - EMC requirements - Part 3-2: Immunity requirements for safety-related systems and for equipment intended to perform safety-related functions (functional safety) - Industrial applications with specified electromagnetic environment EN IEC 61326-3-2:2018

Publication date:   Feb 14, 2019

General information

60.60 Standard published   Nov 30, 2018

CENELEC

CLC/TC 65X Industrial-process measurement, control and automation

European Norm

25.040.40   Industrial process measurement and control | 33.100.20   Immunity

Buying

Published

Language in which you want to receive the document.

Scope

This part of IEC 61326 covers all equipment within the scope of IEC 61326-1, but is limited to
systems and equipment for industrial applications within a specified electromagnetic
environment and intended to perform safety functions as defined in IEC 61508 with SIL 1-3.
The electromagnetic environments encompassed by this product family standard are
industrial, both indoor and outdoor, and based on the requirements of the process industry,
specifically chemical/petrochemical/pharmaceutical manufacturing plants using the mitigation
measures given in Annex C. The difference between the electromagnetic environment
covered by this document compared to the general industrial environment (see IEC 61326-3-
1) is due to the mitigation measures employed against electromagnetic phenomena leading to
a specified electromagnetic environment with test values that have been proven in practice.
The environment of industrial application with a specified electromagnetic environment
typically includes the following characteristics:
– industrial area with limited access;
– limited use of mobile transmitters;
– dedicated cables for power supply and control, signal or communication lines;
– separation between power supply and control, signal or communication cables;
– factory building mostly consisting of metal construction;
– overvoltage/lightning protection by appropriate measures (for example, metal construction
of the building or use of protection devices);
- pipe heating systems driven by AC main power;
- no high-voltage substation close to sensitive areas;
- presence of CISPR 11 Group 2 ISM equipment using ISM frequencies only with low power;
- competent staff;
- periodical maintenance of equipment and systems;
- mounting and installation guidelines for equipment and systems.
Equipment and systems considered as "proven-in-use" according to IEC 61508 or "prior use"
according to IEC 61511 are excluded from the scope of this document.
Fire alarm systems and security alarm systems intended for protection of buildings are
excluded from the scope of this document.

Related legislation

Legislation related to this standard

2004/108/EC

Directive 2004/108/EC of the European Parliament and of the Council of 15 December 2004 on the approximation of the laws of the Member States relating to electromagnetic compatibility and repealing Directive 89/336/EEC

Life cycle

PREVIOUSLY

WITHDRAWN
EN 61326-3-2:2008

NOW

PUBLISHED
EN IEC 61326-3-2:2018
60.60 Standard published
Nov 30, 2018